Severity
Moderate
CPSC recall · Reported May 31, 2005
The recalled cables do not meet the fire resistance standards for cable used in plenum applications. Plenum is the space typically used for air circulation in heating and air cond…
Hitachi Cable Manchester (Hcm), Inc. of Manchester, N.h. recalled The recalled cables typically were installed in data centers and other commercial applica… - a moderate-severity action.
CPSC, Hitachi Cable Manchester Inc. Announce Recall of 25- and 50-Pair Plenum Network Cab… was recalled by Hitachi Cable Manchester (Hcm), Inc. of Manchester, N.h. in May 31, 2005. Reason: The recalled cables do not meet the fire resistance standards for cable used in plenum applications. Plenum i…. Remedy: Cables installed in a plenum application will be removed and replaced. Users should conta…. Verify recall #05184 with the CPSC before acting.
The recall
Hitachi Cable Manchester (Hcm), Inc. of Manchester, N.h. issued this moderate-severity CPSC recall-The recalled cables do not meet the fire resistance standards for cable used in plenum applications. Plenum i….
Sourced from official CPSC enforcement records. Verify recall #05184 with the agency before acting. Full product description, hazard, remedy, and related recalls are below.
This CPSC action (record #05184) was formally reported on May 31, 2005. It is classified under Moderate severity, with a current status of Active. Hitachi Cable Manchester (Hcm), Inc. of Manchester, N.h. is listed as the recalling firm. Federal records list the affected scope as About 1.7 million feet.
The documented reason for this recall is: The recalled cables do not meet the fire resistance standards for cable used in plenum applications. Plenum is the space typically used for air circulation in heating and air conditioning systems. If the cables were exp… Distribution information was not included in the agency filing, so consumers should assume broad potential exposure until the firm publishes point-of-sale details. The remedy documented by the agency is: Cables installed in a plenum application will be removed and replaced. Users should contact HCM to coordinate this work among HCM, the property owner and an installer. Because these products were con… - consumers holding this product should act on that instruction rather than relying on general guidance.
Within the same product category the archive holds 6 closely related recalls, 6 from CPSC - clustering in a narrow category often points to a systemic quality-control or supplier issue rather than a one-off defect. Always verify the recall number against the official agency record before acting.
Where this recall sits in its category - 609 electronics recalls on record
Of 101,704 recalls in the database, 24,878 are high severity, 72,426 moderate, and 4,400 low. This recall is classified moderate severity.
Counts reflect market size and reporting activity, not inherent danger, we do not rank products by risk from raw recall volume.
Severity
Moderate
Affected scope
About 1.7 million feet
Related Recalls
6
6 from same agency
The recalled cables typically were installed in data centers and other commercial applications. The part numbers for the recalled cables are 39419-50 (25-pair, category 5e); 30171-100 (50-pair, category 5e); and 30105-50 (25-pair, category 5). Only HCM brand cables with the following lot numbers are affected by this recall: AE589 and A4309 through A5551. The part number and lot number are printed on the jacket of the cables.
The recalled cables do not meet the fire resistance standards for cable used in plenum applications. Plenum is the space typically used for air circulation in heating and air conditioning systems. If the cables were exposed to a fire source, smoke or fire could spread more quickly than permitted by the standard for this type of cable.
Cables installed in a plenum application will be removed and replaced. Users should contact HCM to coordinate this work among HCM, the property owner and an installer. Because these products were constructed in compliance with HCM's new listing with UL for CMR (riser) cables, they may remain in place if they have already been installed in riser applications. HCM is directly notifying known purchasers about this recall. The 25-pair version of the recalled cable also was manufactured by HCM under a private label arrangement for Superior Essex Inc. Superior Essex has already contacted all affected customers who purchased this cable.
| Attribute | Value |
|---|---|
| Agency | U.S. Consumer Product Safety Commission |
| Severity class | Moderate |
| Status | Active |
| Recall number | 05184 |
| Date reported | May 31, 2005 |
| Date initiated | May 31, 2005 |
| Recalling firm | Hitachi Cable Manchester (Hcm), Inc. of Manchester, N.h. |
| Affected scope | About 1.7 million feet |
| Distribution | Not disclosed |
| Official source | CPSC notice → |
Profile values are sourced directly from the official CPSC enforcement record. Source: U.S. Consumer Product Safety Commission.
What to do with this recall
Cables installed in a plenum application will be removed and replaced. Users should contact HCM to coordinate this work among HCM…
This page summarizes the official CPSC record for research and awareness; it is not legal, medical, or safety advice. Verify with the issuing agency before acting.
Other recalls in the same product category, useful for spotting patterns across the same defect class or manufacturer.
Shenzhen Bopu Product Design Co., Ltd., dba POPOOO, of China · 2026-07-02
· 2026-06-25
· 2026-06-25
· 2026-06-25
School Specialty, LLC, of Greenville, Wisconsin · 2026-06-11
Compare this recall with Projecting LED Finger Light Toys Recalled Due to Risk of Se… →
Every figure on PlainRecalls is rendered directly from official FDA, CPSC and NHTSA recall records, no number is typed in by an editor. This recall: CPSC, reported May 31, 2005. Severity classes follow each agency's own taxonomy (FDA Class I/II/III; CPSC and NHTSA by hazard type), and related-recall context is computed across the full archive. See our editorial standards & corrections policy, the methodology behind these numbers, or report a data error. Data current as of July 2026.