Severity
Moderate
CPSC recall · Reported October 31, 2006
These boilers were manufactured for use with natural gas, but could have a blue tag incorrectly indicating to installers that they are intended for use with LP (propane) gas. If a…
Weil-McLain, of Michigan City, Ind. recalled The recall involves Weil-McLain Ultra 80, Ultra 105, Ultra 155, Ultra 230 and Ultra 310 c… - a moderate-severity action.
Weil-McLain Recalls Ultra Series Boilers for Carbon Monoxide Hazard was recalled by Weil-McLain, of Michigan City, Ind. in October 31, 2006. Reason: These boilers were manufactured for use with natural gas, but could have a blue tag incorrectly indicating to…. Remedy: Consumers who had a Weil-McLain Ultra series boiler installed for use with propane and ha…. Verify recall #07020 with the CPSC before acting.
The recall
Weil-McLain, of Michigan City, Ind. issued this moderate-severity CPSC recall-These boilers were manufactured for use with natural gas, but could have a blue tag incorrectly indicating to….
Sourced from official CPSC enforcement records. Verify recall #07020 with the agency before acting. Full product description, hazard, remedy, and related recalls are below.
This CPSC action (record #07020) was formally reported on October 31, 2006. It is classified under Moderate severity, with a current status of Active. Weil-McLain, of Michigan City, Ind. is listed as the recalling firm. Federal records list the affected scope as About 16,000.
The documented reason for this recall is: These boilers were manufactured for use with natural gas, but could have a blue tag incorrectly indicating to installers that they are intended for use with LP (propane) gas. If an installer connects one of the boilers … Distribution information was not included in the agency filing, so consumers should assume broad potential exposure until the firm publishes point-of-sale details. The remedy documented by the agency is: Consumers who had a Weil-McLain Ultra series boiler installed for use with propane and have not already been contacted by their installer should contact the installer or a heating professional for a … - consumers holding this product should act on that instruction rather than relying on general guidance.
Within the same product category the archive holds 6 closely related recalls, 6 from CPSC - clustering in a narrow category often points to a systemic quality-control or supplier issue rather than a one-off defect. Always verify the recall number against the official agency record before acting.
Where this recall sits in its category - 3,056 household products recalls on record
Of 101,704 recalls in the database, 24,878 are high severity, 72,426 moderate, and 4,400 low. This recall is classified moderate severity.
Counts reflect market size and reporting activity, not inherent danger, we do not rank products by risk from raw recall volume.
Severity
Moderate
Affected scope
About 16,000
Related Recalls
6
6 from same agency
The recall involves Weil-McLain Ultra 80, Ultra 105, Ultra 155, Ultra 230 and Ultra 310 condensing, high-efficient, gas-fired boilers for space heating. The user's manual and installation manual have "Ultra Gas-Fired Water Boiler" on the cover. The boilers are wrapped in a glossy silver/flat black jacket and either stand on the floor or are wall-mounted. The serial numbers range from CP5071716 through CP5327000. When the panel on the front of the boiler is removed, a bar-coded label with the serial number is located on the lower right hand side of the boiler itself. "Weil-McLain" is written on the front panel of the boilers.
These boilers were manufactured for use with natural gas, but could have a blue tag incorrectly indicating to installers that they are intended for use with LP (propane) gas. If an installer connects one of the boilers to LP gas without installing a propane conversion kit, carbon monoxide (CO) can build up due to incomplete combustion, posing a risk of CO poisoning.
Consumers who had a Weil-McLain Ultra series boiler installed for use with propane and have not already been contacted by their installer should contact the installer or a heating professional for a free safety inspection. If the boiler was not installed with a propane conversion kit, one will be installed at the time of the inspection at no charge. Heating professionals may contact Weil McLain Technical Service at (219) 879-6561 for more information.
| Attribute | Value |
|---|---|
| Agency | U.S. Consumer Product Safety Commission |
| Severity class | Moderate |
| Status | Active |
| Recall number | 07020 |
| Date reported | October 31, 2006 |
| Date initiated | October 31, 2006 |
| Recalling firm | Weil-McLain, of Michigan City, Ind. |
| Affected scope | About 16,000 |
| Distribution | Not disclosed |
| Official source | CPSC notice → |
Profile values are sourced directly from the official CPSC enforcement record. Source: U.S. Consumer Product Safety Commission.
What to do with this recall
Consumers who had a Weil-McLain Ultra series boiler installed for use with propane and have not already been contacted by their i…
This page summarizes the official CPSC record for research and awareness; it is not legal, medical, or safety advice. Verify with the issuing agency before acting.
Other recalls in the same product category, useful for spotting patterns across the same defect class or manufacturer.
Cooper Lighting, LLC, of Peachtree City, Georgia · 2026-07-02
· 2026-07-02
· 2026-07-02
· 2026-06-25
· 2026-06-25
Compare this recall with Cooper Lighting Recalls Metalux Optimized High Bay LED Ligh… →
Every figure on PlainRecalls is rendered directly from official FDA, CPSC and NHTSA recall records, no number is typed in by an editor. This recall: CPSC, reported October 31, 2006. Severity classes follow each agency's own taxonomy (FDA Class I/II/III; CPSC and NHTSA by hazard type), and related-recall context is computed across the full archive. See our editorial standards & corrections policy, the methodology behind these numbers, or report a data error. Data current as of July 2026.