Siemens Recalls Circuit Breakers Due to Fire Hazard

Reported: September 23, 2010 Initiated: September 23, 2010 #10354

Product Description

This recall involves Siemens and Murray 15 through 50 AMP single and double pole circuit breakers, load centers (circuit breakers that come with an electrical panel), and meter combos (contain a load center and a meter socket). "Siemens" or "Murray," date codes 0610 or 0710 and the catalog number are printed on a label on the side of the circuit breakers. Date codes between June 2010 through August 2010 are stamped on the inside of the metal box of the load centers and meter combos. The catalog number for the load centers and meter combos is printed on a label inside the metal box door and on the packaging. Product Date Codes Catalog Numbers Circuit Breakers 0610, 0710 Q115, Q120, Q130, Q215, Q230, Q250, MP115, MP115U, MP120, MP130, MP215, MP230, MP230U, MP250 Load Centers Jun 23 2010 - Aug 25 2010 G2020B1100CP, G3030B1100CP, G4040B1200CUSGP, LC4040B1200P, G3040B1200CP, G3040L1200CP, G4040B1200CP, G3030B1150CP, W3040B1200CP, G1624L1125CP, W4040B1200CP Meter Combo Jun 23 2010 - Aug 25 2010 JA2040B1200S

Reason for Recall

The recalled circuit breakers have a spring clip that can break during normal use, leading to a loss of force to maintain a proper electrical connection in the panelboard. This can lead to excessive temperature, arcing or thermal damage at the connection point, and damage to the panelboard's electrical insulation and can result in a fire, property damage, or personal injury.

Remedy

Consumers should immediately contact Siemens for a free inspection by an electrician and a free replacement product.

Details

Units Affected
About 2.2 million

Frequently Asked Questions

What product was recalled?
This recall involves Siemens and Murray 15 through 50 AMP single and double pole circuit breakers, load centers (circuit breakers that come with an electrical panel), and meter combos (contain a load center and a meter socket). "Siemens" or "Murray," date codes 0610 or 0710 and the catalog number are printed on a label on the side of the circuit breakers. Date codes between June 2010 through August 2010 are stamped on the inside of the metal box of the load centers and meter combos. The catalog number for the load centers and meter combos is printed on a label inside the metal box door and on the packaging. Product Date Codes Catalog Numbers Circuit Breakers 0610, 0710 Q115, Q120, Q130, Q215, Q230, Q250, MP115, MP115U, MP120, MP130, MP215, MP230, MP230U, MP250 Load Centers Jun 23 2010 - Aug 25 2010 G2020B1100CP, G3030B1100CP, G4040B1200CUSGP, LC4040B1200P, G3040B1200CP, G3040L1200CP, G4040B1200CP, G3030B1150CP, W3040B1200CP, G1624L1125CP, W4040B1200CP Meter Combo Jun 23 2010 - Aug 25 2010 JA2040B1200S. Units affected: About 2.2 million.
Why was this product recalled?
The recalled circuit breakers have a spring clip that can break during normal use, leading to a loss of force to maintain a proper electrical connection in the panelboard. This can lead to excessive temperature, arcing or thermal damage at the connection point, and damage to the panelboard's electrical insulation and can result in a fire, property damage, or personal injury.
What should consumers do?
Consumers should immediately contact Siemens for a free inspection by an electrician and a free replacement product.
Which agency issued this recall?
This recall was issued by the CPSC on September 23, 2010. Severity: Moderate. Recall number: 10354.