CPSC recall · Reported November 13, 2006
If the fire extinguisher is dropped horizontally from a height of approximately 2 to 3 feet, the pick-up tube could crack at the threads between the pick-up tube adaptor and the s…
Ansul Incorporated, of Marinette, Wis. recalled The recall involves K-GUARD® Wet Chemical, FLAG FIRE® KITCHEN ONE® Wet Chemical, FLAG FIR… - a moderate-severity action.
ANSUL Recalls Fire Extinguisher that Could Fail to Operate was recalled by Ansul Incorporated, of Marinette, Wis. in November 13, 2006. Reason: If the fire extinguisher is dropped horizontally from a height of approximately 2 to 3 feet, the pick-up tube…. Remedy: Pick-up tube replacements will be performed during routine annual maintenance. The pick-u…. Verify recall #07507 with the CPSC before acting.
The recall
Ansul Incorporated, of Marinette, Wis. issued this moderate-severity CPSC recall-If the fire extinguisher is dropped horizontally from a height of approximately 2 to 3 feet, the pick-up tube….
Sourced from official CPSC enforcement records. Verify recall #07507 with the agency before acting. Full product description, hazard, remedy, and related recalls are below.
This CPSC action (record #07507) was formally reported on November 13, 2006. It is classified under Moderate severity, with a current status of Active. Ansul Incorporated, of Marinette, Wis. is listed as the recalling firm. Federal records list the affected scope as About 154,000.
The documented reason for this recall is: If the fire extinguisher is dropped horizontally from a height of approximately 2 to 3 feet, the pick-up tube could crack at the threads between the pick-up tube adaptor and the stainless steel tube. If a pick-up tube i… Distribution information was not included in the agency filing, so consumers should assume broad potential exposure until the firm publishes point-of-sale details. The remedy documented by the agency is: Pick-up tube replacements will be performed during routine annual maintenance. The pick-up tube assembly is inside the extinguisher and cannot be visually inspected without de-pressurizing and disass… - consumers holding this product should act on that instruction rather than relying on general guidance.
Within the same product category the archive holds 6 closely related recalls, 6 from CPSC - clustering in a narrow category often points to a systemic quality-control or supplier issue rather than a one-off defect. Always verify the recall number against the official agency record before acting.
Where this recall sits in its category - 3,056 household products recalls on record
Of 101,704 recalls in the database, 24,878 are high severity, 72,426 moderate, and 4,400 low. This recall is classified moderate severity.
Counts reflect market size and reporting activity, not inherent danger, we do not rank products by risk from raw recall volume.
Severity
Moderate
Affected scope
About 154,000
Related Recalls
6
6 from same agency
The recall involves K-GUARD® Wet Chemical, FLAG FIRE® KITCHEN ONE® Wet Chemical, FLAG FIRE® Water and SENTRY® Water Fire Extinguishers manufactured and shipped between May 2003 and September 9, 2005. The recall program involves pick-up tube replacements in the following extinguishers: Brand Model Part Number(s) K-GUARD® Wet Chemical K01-1 430849 (UL) 430850 (ULC) K01-2 432843 (UL) 432848 (ULC) SENTRY® Water W02-1 430847 (English) 430848 (Spanish/English) FLAG FIRE® KITCHEN ONE® Wet Chemical KS-6000 552055 (UL) 552500 (ULC) FLAG FIRE® Water PWS-25G 552050 (UL) 552501 (ULC) Model numbers can be found on the fire extinguisher labels. Affected models meet the following criteria: The year 2004 or 2005 is stamped on the hanger hook attachment on the shell. For 2003 models, information on specific serial numbers included in the recall can be found at www.ansul.com for the K-GUARD Wet Chemical and SENTRY Water extinguishers, or at www.pyrochem.com for the FLAG FIRE and KITCHEN ONE Wet Chemical extinguishers. Contact the firm to determine if your extinguisher is included in this replacement program.
If the fire extinguisher is dropped horizontally from a height of approximately 2 to 3 feet, the pick-up tube could crack at the threads between the pick-up tube adaptor and the stainless steel tube. If a pick-up tube is cracked, the extinguisher can fail to discharge properly when activated, which can put users at risk during a fire.
Pick-up tube replacements will be performed during routine annual maintenance. The pick-up tube assembly is inside the extinguisher and cannot be visually inspected without de-pressurizing and disassembling the extinguisher. This work should only be done by an authorized ANSUL® distributor. Owners concerned about an extinguisher prior to the scheduled maintenance, due to signs of physical damage such as dents or scratches, should contact their authorized ANSUL® distributor to request a free replacement.
| Attribute | Value |
|---|---|
| Agency | U.S. Consumer Product Safety Commission |
| Severity class | Moderate |
| Status | Active |
| Recall number | 07507 |
| Date reported | November 13, 2006 |
| Date initiated | November 13, 2006 |
| Recalling firm | Ansul Incorporated, of Marinette, Wis. |
| Affected scope | About 154,000 |
| Distribution | Not disclosed |
| Official source | CPSC notice → |
Profile values are sourced directly from the official CPSC enforcement record. Source: U.S. Consumer Product Safety Commission.
What to do with this recall
Pick-up tube replacements will be performed during routine annual maintenance. The pick-up tube assembly is inside the extinguish…
This page summarizes the official CPSC record for research and awareness; it is not legal, medical, or safety advice. Verify with the issuing agency before acting.
Other recalls in the same product category, useful for spotting patterns across the same defect class or manufacturer.
Cooper Lighting, LLC, of Peachtree City, Georgia · 2026-07-02
· 2026-07-02
· 2026-07-02
· 2026-06-25
· 2026-06-25
Compare this recall with Cooper Lighting Recalls Metalux Optimized High Bay LED Ligh… →
Every figure on PlainRecalls is rendered directly from official FDA, CPSC and NHTSA recall records, no number is typed in by an editor. This recall: CPSC, reported November 13, 2006. Severity classes follow each agency's own taxonomy (FDA Class I/II/III; CPSC and NHTSA by hazard type), and related-recall context is computed across the full archive. See our editorial standards & corrections policy, the methodology behind these numbers, or report a data error. Data current as of July 2026.