CPSC recall · Reported December 18, 2014
Schneider Electric Recalls PowerPact J-Frame Circuit Breakers Due to Fire, Burn, Electrical Shock Hazards
The circuit breaker will not trip during an overload condition, posing a risk of fire, burns and electrical shock.
Schneider Electric USA Inc., of Columbia, Mo., and Tlaxcala, Mexico recalled The recall involves PowerPact J-frame molded case circuit breakers with thermal-magnetic ….
Schneider Electric Recalls PowerPact J-Frame Circuit Breakers Due to Fire, Burn, Electric… was recalled by Schneider Electric USA Inc., of Columbia, Mo., and Tlaxcala, Mexico in December 18, 2014. Reason: The circuit breaker will not trip during an overload condition, posing a risk of fire, burns and electrical s…. Remedy: Consumers should immediately stop using the recalled circuit breakers and contact Schneid…. Verify recall #15050 with the CPSC before acting.
The recall
Schneider Electric USA Inc., of Columbia, Mo., and Tlaxcala, Mexico issued this CPSC recall-The circuit breaker will not trip during an overload condition, posing a risk of fire, burns and electrical s….
- None
- agency class
- December 18, 2014
- reported
Sourced from official CPSC enforcement records. Verify recall #15050 with the agency before acting. Full product description, hazard, remedy, and related recalls are below.
Recall Insight
This recall's affected scope, documented in the Recall Profile below, stays within a single-region or limited-distribution footprint. Distribution information was not included in the agency filing, so consumers should assume broad potential exposure until the firm publishes point-of-sale details. Consumers holding this product should act on the agency's documented remedy above rather than relying on general guidance.
Within the same product category the archive holds 6 closely related recalls, 6 from CPSC - clustering in a narrow category often points to a systemic quality-control or supplier issue rather than a one-off defect. Always verify the recall number against the official agency record before acting.
Household Products recalls over time
Where this recall sits in its category - 3,089 household products recalls on record
Product description
The recall involves PowerPact J-frame molded case circuit breakers with thermal-magnetic trip units. The circuit breakers are made of black plastic and have a three-position breaker handle that indicates whether the breaker is off, on or tripped. The recalled circuit breakers are rated for 150 to 250 amps, have interruption ratings of D, G, J, L and R. They were manufactured in two pole and three pole configurations with either lug-in/lug-out or plug-in (I-Line) style connectors. Brand name "Schneider Electric" or "Square D" is on a yellow sticker above the breaker handle and on the top of a label on the side of the circuit breaker. A label on the front of the circuit breaker to the left of the breaker handle has the catalog number at the top. The number also appears on a label on the side of the breaker. Schneider Electric catalog numbers begin with "NJ" and Square D catalog numbers begin with "J." A label on the front of the circuit breaker to the right of the breaker handle has the date code in the lower right corner. Recalled circuit breakers were manufactured from March 26, 2014 through September 26, 2014 and have date codes 14131 through 14395. The date codes are in the YYWWD format (example: 14131 = year 2014, week 13, day of the work week 1/ Monday). Breakers with following catalog numbers are being recalled: Catalog Number Breaker Type (N)JDX26XXX 2 Pole (N)JGX26XXX 2 Pole (N)JJX26XXX 2 Pole (N)JLX26XXX 2 Pole (N)JDX36XXX 3 Pole (N)JGX36XXX 3 Pole (N)JJX36XXX 3 Pole (N)JLX36XXX 3 Pole (N)JRX36XXX 3 Pole
Reason for recall
The circuit breaker will not trip during an overload condition, posing a risk of fire, burns and electrical shock.
Remedy, what to do
Consumers should immediately stop using the recalled circuit breakers and contact Schneider Electric for either a free replacement circuit breaker and a credit of up to $300 per address to cover labor costs for installation by a certified electrician or a handle update kit and a credit of up to $150 per address to cover labor costs for installation by a certified electrician.
Recall Profile
| Attribute | Value |
|---|---|
| Agency | U.S. Consumer Product Safety Commission |
| Severity class | Not classified by agency |
| Status | Active |
| Recall number | 15050 |
| Date reported | December 18, 2014 |
| Date initiated | December 18, 2014 |
| Recalling firm | Schneider Electric USA Inc., of Columbia, Mo., and Tlaxcala, Mexico |
| Affected scope | About 62,500 |
| Distribution | Not disclosed |
| Official source | CPSC notice → |
Profile values are sourced directly from the official CPSC enforcement record. Source: U.S. Consumer Product Safety Commission.
What to do with this recall
Consumers should immediately stop using the recalled circuit breakers and contact Schneider Electric for either a free replacemen…
- Check the recall number (15050) and product description against the item you own. Search the archive
- Confirm the current status and remedy on the official CPSC notice before acting. CPSC notice
- Follow the documented remedy (refund, replacement, repair, or disposal) rather than general advice. What to do next
This page summarizes the official CPSC record for research and awareness; it is not legal, medical, or safety advice. Verify with the issuing agency before acting.
Frequently Asked Questions
What product was recalled? ▼
Why was this product recalled? ▼
What should consumers do? ▼
Which agency issued this recall? ▼
How do I report an injury from a recalled product? ▼
Nationwide recalls with similar severity or category timing
Consumer-product notices outside this firm and state, matched by severity timing and product category.
Similar severity · nearest report date
Same archive severity grade, closest by report date among other firms and states.
Similar Household Products · nearest report date
Same product category, closest by report date among other firms and states (deduped against the severity set).
Compare this recall with CCM Hockey U.S. Recalls FMHVR Hybrid Visors and ACCHVR Repl… → · All Household Products recalls
Methodology · Corrections · Archive as of August 2026